600 StarCool Alarm Codes And Actions

600 No control sensors
Description Supply Air Sensor 1, Supply Air Sensor 2, Return Air Sensor and Evaporator
Sensor are all malfunctioning.
Cause Alarm indicates that all control-relevant sensors are defective or unreliable. See
also “Temperature control” p. 19 and “Expansion valve control” p. 19
Trouble
shooting
Possible causes:
  • Supply Air Sensor 1, Supply Air Sensor 2, Return Air Sensor and Evaporator Sensor are all malfunctioning.
  • X22, X23, X24 and X25 cable is defective.
  • Main controller defective.
Accompanied alarms:
  • AL 100 to AL 108.
Trouble shooting

  1. Verify all other sensor alarms AL 100 to AL 3XX and try to remove these alarms.
  2. If this alarm remains active, replace main controller.
Criteria No valid control sensor values